Time response: overshoot, settling time, steady-state error

Control performance is described by the shape of the response to a step input. What the numbers written in a specification mean.

GROUND EMBEDDED · NOTEControl Engineering 05Time responseTargetKpKiKd

Measures

TargetP too high: ringsRight: fast, stableGain too low: slowTime
The values read from a step response. Overshoot and settling time change with the gain.
Measure Meaning
Rise time From 10% to 90% of the final value
Overshoot The largest fraction by which it exceeds the final value (%)
Settling time The time from which it stays within ±2% (or 5%) of the final value
Steady-state error The error left after enough time has passed

Relation to a second-order system

  • The smaller the damping ratio ζ, the larger the overshoot (about 5% at ζ = 0.7)
  • The larger the natural frequency ωn, the faster

A specification such as "overshoot 5% or less, settling time 200 ms or less" fixes targets for ζ and ωn, and the gains are chosen to match.

3D labRun what you have read so far→

Steady-state error

With P control alone, a loaded motor stops a little below the target speed, because output only exists while there is error. The integral (I) term accumulates error and removes this gap.

Measuring

On a real board, change the target as a step, log the output (telemetry) and plot it. Overlaying it on the simulated response shows the difference between model and reality.